Guardian Fire Suppression Systems

Model G300-B

image101

Operation: Electronic

Coverage: Electric Ranges up to 42" wide x 24" Deep or 864 Sq. In.

Hood: Any standard residential hood with a single light and fan in the center that meets the same range size requirements. Bottom of the hood must have a minimum height of 18" to the range and cannot exceed 30".

Nozzles: Requires a minimum height of 18" to the range and cannot exceed 30:.

Sensors: Requires a minimum height of 22" from the sensor to range and a maximum of 35".

Fuel Shutoff: Each system is UL listed with a gas or electric fuel shutoff, which is supplied, and can be wired or wirelessly installed.


Model G500-B

image102

Operation: Electronic

Coverage: Electric Ranges up to 42" wide x 24" deep or 1,008 Sq. In.

Gas ranges 36" wide x 24" deep or 864 sq. in.

Hood: Any standard residential hood with a single light and fan in the center that meets the same range requirements. Bottom of the hood must have a minimum height of 18" to the range and cannot exceed 30".

Nozzles: Requires a minimum height of 18" from the tip of the nozzle to the range and a maximum of 31".

Sensors: New plug and play sensors that require a minimum height of 22" from the sensor to range and a maximum of 35".

Circuit Board: New and improved circuit board with plug and play features.

Fuel Shutoff: Each system is UL Listed with a gas or electric fuel shutoff, which is supplied, and can be wired or wirelessly installed. 

Model 1384-B

image103

Operation:  Mechanical

Coverage: Electric and gas ranges may not exceed a width of 36" wide x 24" deep or 864 sq. in.

Hood: Any standard residential hood with a single light and filter in the center that meets the same range requirements. The bottom of the hood cannot exceed 30" from the range top.

Nozzles: The nozzle tip must be at least 18" above the range with a maximum of 28". 

G600-B

image104

Operation: Electronic 

Coverage: Electric and gas ranges not to exceed 30" wide x 24" deep or 864 sq. in.

Hood: Works with any standard stove microwave range/hood, as well as some hoods with a full filter bank underneath. 

Circuit Board: New and improved circuit board with plug and play features.

G600B-C

image105

Operation: Electronic. This system is designed for mobile applications such as RV's and boats.

Coverage: Electric or gas ranges not to exceed 30" wide x 24" deep or 864 sq. in.

Hood: Works with any standard over the stove microwave/range hood, as well as some high hoods with full filter bank underneath.

Circuit Board: New and improved circuit board with plug and play features. 

General Information

image106

Superior Fire Suppression For Commercial Occupancies Where Residential Style Appliances Are In Use.


Over 400,000 systems installed and supported by our distributors worldwide since 1985.


Pre-Assembled  -  Pre-Engineered

 When a fire occurs, the sensors will activate at a preset temperature sending a signal to the CPU board which releases the valve assembly discharging the system.

Find out more